Load Calculator

Horsepower to amps and back, kW and kVA to amps, at any voltage. Motors get the NEC full-load current and the branch circuit sized from it.

NEC 2017 · Tables 430.247, 430.248, 430.250 and 430.52

01

Inputs

What is the load?

Motors use the NEC full-load current tables.

What do you know?
System
V
Power factor and efficiency
%

From the nameplate. Left blank, a motor is figured at 0.85 power factor and 90% efficiency for the formula estimate. The NEC table value does not depend on either.

02

Result

Working it out…

Or just describe it Ask MJK runs the calculator for you

How horsepower becomes amps

There are two honest answers to “how many amps does this motor draw?”, and they are used for different things.

The NEC table value. For a standard motor, the Code gives a full-load current by horsepower and voltage: Table 430.250 for three-phase, Table 430.248 for single-phase and Table 430.247 for DC. Section 430.6(A)(1) says to size the branch-circuit conductors and the short-circuit protection from that table value, not from the nameplate. That is the figure this calculator leads with. The 115, 230, 460 and 575 volt columns cover 110–120, 220–240, 440–480 and 550–600 volt systems, so a motor on a 480 volt system is read from the 460 volt column.

The formula. A motor’s actual current depends on its efficiency and power factor:

Three-phase: I = (HP × 746) ÷ (√3 × V × efficiency × power factor)
Single-phase: I = (HP × 746) ÷ (V × efficiency × power factor)
DC: I = (HP × 746) ÷ (V × efficiency)

The table runs higher than the formula for most modern motors. That is deliberate: it has to cover every motor of that rating. Use the formula, with the nameplate values, to estimate what a particular motor will draw.

Sizing the motor circuit

When the horsepower and voltage are in the tables, the result also gives the branch circuit for a single continuous-duty motor:

  • Conductors: an ampacity of at least 125% of the table full-load current (430.22).
  • Short-circuit and ground-fault protection: no larger than the Table 430.52 percentage of full-load current: 250% for an inverse time breaker, 175% for a dual element (time-delay) fuse, 300% for a nontime delay fuse; 150% for DC motors. Where that does not land on a standard size, the next standard size up is allowed (430.52(C)(1) Exception No. 1, sizes from 240.6(A)).
  • Overloads are different: they are set from the motor’s nameplate current (430.6(A)(2), 430.32), so they are not in the result.

These are maximums and minimums from the Code, not a design. Wound-rotor motors, Design B energy-efficient motors on instantaneous-trip breakers, motors that start hard, and several motors on one feeder each have rules of their own.

kW, kVA and amps

For anything that is not a motor, choose Other load and enter what you know:

Three-phase: kVA = √3 × V × I ÷ 1000
Single-phase: kVA = V × I ÷ 1000
kW = kVA × power factor

A heater or other resistive load has a power factor of 1, so its kW and kVA are the same. A transformer is rated in kVA, so its full-load current needs no power factor at all. The result also shows the load at 125%, the figure used to size conductors and overcurrent protection for a load that runs three hours or more (210.19(A)(1), 215.2(A)(1)).

From the numbers to the job

Need it installed?

The calculator gives you the numbers. For the drawings, the permit and the installation, talk to a licensed commercial and industrial contractor.