Conduit Fill Calculator
Mix conductor sizes and insulation types in any conduit and get the fill percent, the limit that applies and the smallest trade size that passes.
NEC 2017 · Chapter 9, Tables 1, 4, 5, 5A and 8
Result
Working it out…
General information, not engineering design. The 2017 NEC is used here; your city may be on another edition, and the inspector has the final say.
How conduit fill is calculated
Conduit fill is the share of a conduit’s inside area taken up by the conductors in it, insulation included. The Code limits it so the wire can be pulled without damage and can shed heat once it is in. The limit depends on how many conductors there are (NEC Chapter 9, Table 1):
| Conductors in the conduit | Maximum fill |
|---|---|
| One | 53% |
| Two | 31% |
| Over two | 40% |
| Any number, in a nipple 24 in. or shorter | 60% |
The calculator adds up the area of every conductor from Chapter 9 Table 5 (Table 5A for compact conductors, Table 8 for bare ones), divides by the conduit’s total inside area from Table 4, and compares the result with the limit. It then does the same for every trade size of that conduit, so you can see the smallest one that passes and how much room the next size up would leave.
Fill % = total conductor area ÷ conduit inside area × 100
What counts, and what people miss
- The ground counts. Equipment grounding and bonding conductors are part of the fill, insulated or bare (Table 1, Note 3).
- A cable is one conductor. A multiconductor cable is treated as a single conductor using its actual outside diameter; for an oval cable, the larger dimension (Notes 5 and 9).
- Same-size conductors round up. When every conductor is the same size, a result of 0.8 of a conductor or more counts as a whole one (Note 7). That is why this calculator agrees with the tables in Informative Annex C.
- Three conductors can jam. When the conduit’s inside diameter is 2.8 to 3.2 times the conductor diameter, three conductors can wedge side by side in a bend (Informational Note No. 2). The calculator warns you.
- Fill is not ampacity. More than three current-carrying conductors in a raceway have their ampacity reduced (310.15(B)(3)(a)), whatever the fill.
Table 1 assumes a reasonable pull. A long run or a lot of bends is a good reason to go up a size even when the percentage passes.
Copper or aluminum?
For fill it makes no difference: the Code lists one set of dimensions per insulation type, and a 4/0 THHN conductor takes the same space in either metal. Compact-stranded conductors, which are common in aluminum, are smaller and have their own table (5A), so they are listed separately here.
From the numbers to the job
Need it installed?
The calculator gives you the numbers. For the drawings, the permit and the installation, talk to a licensed commercial and industrial contractor.